GCE HV BMS Configuration:
One complete set of HV 75S240V 50A BMS includes:
Master BMS, Model#: RBMS08-D75S-50A, and its wire accessories, include 6p temperature sensing wires and 16p voltage sensing wires.
There are two different models for integrated BMS, one is a standalone model while the other one is parallel with its cost slightly higher than the standalone model.
GCE HV Integrated Master BMS and Accessories:
30-75S Integrated BMS
Voltage range:96V-240V
Current:50A/100A
Communication:CAN & RS485
Design: Master & slave all in one.
Temperature acquisition wire
Standard length is 600mm,900mm,1200mm
There are 3 temperature sensing probes per 15S wires. In total, there are 12 probes in 60S and 15 probes in 75S.
Voltage acquisition wire
Standard length is 600mm,900mm,1200mm
GCE integrated BMS Characteristics:
※ Perfect self-checking and running status checking function, with HMI display screen, system running information is clear at a glance.
| ※ Abundant communication interfaces---multiple RS485, CAN, Ethernet, dry contact input and output interfaces, supporting communication with most PCS and monitoring servers on the market. |
GCE integrated BMS Technical parameters:
Item | Specifications and parameters | |
System operating voltage range | 120 - 370 VDC | |
Startup mode | DC start | |
balance | Equilibrium type | Passive resistance equalization |
Balanced current | 100mA ± 10mA (when cell at 3.50V) | |
Sampling accuracy | ± 2℃ | |
Voltage sampling | Sampling accuracy | single-cell ±20mV |
Communication mode | Can: 1 channel (communication with PCs / UPS) | |
RS485: 1 channel (communication with upper computer / PCS / UPS) | ||
Display mode | 6-digit LED indicator, including | |
1-bit fault indication, 1-bit operation indication, 4-bit SOC power indication | ||
HMI display: optional 3.5 inch | ||
Rated current | 50A/100A | |
(be selected according to customer needs) | ||
Short circuit protection | Support 7.5KA 20ms | |
Maximum overload capacity | 50A system transient: 70A/10S | |
100A system transient: 150A/10S | ||
Alarm level | one Level | |
Protection level | two levels | |
Level 1 cut-off charge/discharge | ||
Level 2 micro cut-off switch, system power down | ||
Power consumption | ≤10W | |
Weight | 4.5kg | |
Withstand voltage rating | 1800VDC 1mA 1min | |
Safety certification | Comply with CE certification standards | |
Operating temperature | -20~60℃ | |
Operating humidity range | <90 RH(40℃±2℃) |
Download linkage of Specification:
GCE 30S-75S integrated BMS specification Ch-EN V2...
High Voltage BMS Application:
FAQs about GCE HV BMS: